LatestProducts

                            LC1-D AC Contactor

                            LC1-D AC Contactor

                            LC1-D AC Contactor

LC1-D AC Contactor

d ac
INQUIRY PRECISE INQUIRY
Description

Basic Info
  • Model NO.: CEC2
  • Type: Ac Contactors
  • Origin: China
  • Electricity Type: AC
  • Trademark: CEA
Product Description
CEC2 series AC contactors are suitable for using in the circuits up to the rated voltage 660V AC 50Hz or 60Hz, rated current up to 95A, for making, breaking, frequently starting a controlling the AC motor. Combined with the auxiliary contact block, timer delay & machineinterlocking device etc, It becomes the delay conductor, mechanical interlocking conductor, star-delta starter with the thermal relay, it is combined into the electromagnetic starter. The conductor is produced according to IEC 60947, EN60947.
Specifications
Type CEC2-09 CEC2-12 CEC2-18 CEC2-25 CEC2-32
Rated Working Current
(A)
 AC3 9 12 18 25 32
AC4 3.5 5 7.7 8.5 12
AC3 Capacity of Phase
3 Squirrel-cage Motor
AC3(kW)
220/230V 2.2 3 4 5.5 7.5
380/400V 4 5.5 7.5 11 15
415V 4 5.5 9 11 15
500V 5.5 7.5 10 15 18.5
660/690V 5.5 7.5 10 15 18.5
Rated Heat Current(A) 20 20 32 40 50
Electrical Life AC3×10 4 100 100 100 100 80
AC4×10 4 20 20 20 20 20
Mechanical Life ×10 4 1000 1000 1000 1000 810
No . of The Contacts 3P+NO

Type CEC2-40 CEC2-50 CEC2-65 CEC2-80 CEC2-95
Rated Working Current
(A)
AC3 40 50 65 80 95
AC4 18.5 24 28 37 44
AC3 Capacity of Phase
3 Squirrel-cage Motor
AC3(kW)
220/230V 11 15 18.5 22 25
380/400V 18.5 22 30 37 45
415V 22 25 37 45 55
500V 22 30 37 55 55
660/690V 30 33 37 45 55
Rated Heat Current(A) 60 80 80 125 125
Electrical Life AC3×10 4 80 60 60 60 60
AC4×10 6 15 15 15 10 10
Mechanical Life ×10 6 800 800 800 600 600
No . of The Contacts 3P+NC+NO
 
Standard Control Circuit Voltage
Volts(VAC) 24 42 48 110 220 230 240 380 400 415 440 550 660
50Hz B5 D5 E5 F5 M5 P5 U6 Q5 V5 N5 R5 S5 Y5
60Hz B6 D6 E6 F6 M6 - U6 Q6 - - R6 - -
50/60Hz B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7 - -
 
Type CEC2-115 CEC2-150 CEC2-170 CEC2-205 CEC2-245 CEC2-300 CEC2-410 CEC2-475 CEC2-620
Rated Working Current (A) AC3 115 150 170 205 245 300 410 475 620
AC4 52 60 75 85 105 117 138 147 180
AC3 Capacity of Phase 3 Squirrel-cage Motor AV3(kW) 220/230V 30 40 55 63 75 100 110 147 200
380/400V 55 75 90 110 132 160 220 265 335
415V 59 80 100 110 132 180 220 280 375
500V 75 90 110 129 160 200 250 355 400
660/690V 80 100 110 129 160 220 280 355 450
Rated Heat Current (A) 200 250 250 275 315 400 500 700 1000
Electrical Life AC3×10 4 200 60 60 50 50 50 30 30 20
AC4×10 4 15 15 15 15 15 15 8 8 5
Mechanical Life×10 6 300 300 300 300 300 300 100 100 100